AC Inrush Current Limiter
SKU:ICL-16R
Manufacturer:Mean Well
The Mean Well ICL-16R is a 16A inrush current limiter designed for DIN-rail mounting, engineered to suppress high peak currents during the startup of capacitive or inductive loads. By reducing initial surges, it prevents the nuisance tripping of circuit breakers and allows for the efficient connection of multiple devices to a single AC line.
Key Features
- 16A current limiting capacity suitable for various power applications
- Integrated bypass relay and control circuit to minimize heat dissipation and improve reliability over standard NTC-based solutions
- Built-in thermal protection for enhanced system safety and component longevity
- Standard DIN-rail mountable design for easy integration into industrial control cabinets
Applications
The ICL-16R is specifically designed for use with switching power supplies and LED drivers. Its ability to manage high peak currents makes it an essential component for stabilizing power distribution in systems where multiple inductive or capacitive consumers are connected to the same circuit.
Key Features
- 16A current limiting capacity suitable for various power applications
- Integrated bypass relay and control circuit to minimize heat dissipation and improve reliability over standard NTC-based solutions
- Built-in thermal protection for enhanced system safety and component longevity
- Standard DIN-rail mountable design for easy integration into industrial control cabinets
Applications
The ICL-16R is specifically designed for use with switching power supplies and LED drivers. Its ability to manage high peak currents makes it an essential component for stabilizing power distribution in systems where multiple inductive or capacitive consumers are connected to the same circuit.
AC Continuous Rated Current: 16A
AC Input Power: 3680VA (16A x 230VAC)
AC Line Frequency: 47 ~ 63Hz
Allowed Capacitive Load: 2500μF max.
Dimensions (W x H x D): 35 x 90 x 54.5 mm
Input Voltage: 180 ~ 264VAC
Inrush Current Limiting: 23A
Internal Protection: Thermal fuse protects against overload and fire
Internal Relay Limiting Time: 300 ± 50ms
Mounting: DIN Rail TS-35/7.5 or 15
Operating Altitude: 5000 meters
Safety Standards: LVD BS EN/EN62368-1 approved
Working Humidity: 20 ~ 90% RH non-condensing
Working Temperature: -30 ~ +70°C
AC Input Power: 3680VA (16A x 230VAC)
AC Line Frequency: 47 ~ 63Hz
Allowed Capacitive Load: 2500μF max.
Dimensions (W x H x D): 35 x 90 x 54.5 mm
Input Voltage: 180 ~ 264VAC
Inrush Current Limiting: 23A
Internal Protection: Thermal fuse protects against overload and fire
Internal Relay Limiting Time: 300 ± 50ms
Mounting: DIN Rail TS-35/7.5 or 15
Operating Altitude: 5000 meters
Safety Standards: LVD BS EN/EN62368-1 approved
Working Humidity: 20 ~ 90% RH non-condensing
Working Temperature: -30 ~ +70°C